6.5.4

ADIO Alarms Detail

6.5.4.1

View Details

This menu item enables the user to select an ADIO device (i.e., Cordex Smart Peripheral) that
is connected to the CXC and view the alarms with respect to: Cell Deviation, Current, Voltage,
Temperature, and Comms.

6.5.5

Alarm Hysteresis

6.5.5.1

Voltage

Voltage Hysteresis applies only to Voltage Alarms (6.5.3.5). This value is the voltage range
where the alarm can clear or activate. For example, if the low voltage alarm activates at 43.00V,
having a voltage hysteresis of 0.50V means it will clear when the voltage reaches 43.50V.

6.5.5.2

Time

Time Hysteresis is the amount of time in seconds that the condition has to be true before the
alarm is enunciated. In the example above, if the value of time hysteresis is 5 seconds, the
voltage must be below 43.00V for at least 5 seconds before the alarm is activated. Similarly, to
clear the alarm, the voltage must be above 43.50V for 5 seconds.

This feature is used only for the following:

Current, Voltage, Battery, and Temperature alarms

HVSD and CEMF controls.

6.5.6

Alarm Tone

This feature is found under the Global Alarm Configuration menu (submenu of Alarms) and the tone is enabled by
default. The Supervisor may enable/disable the audible alarm buzzer (tone).

Figure 44–Global Alarm Configuration web interface window