Series 6A Operation & Maintenance – Calibration & Commissioning

6A O & M : 14

Series 6A with and without HART communications

Operation and Maintenance Manual, 09/2008, A5E00756809-03

Overview of diagnostics values

No.

Abbreviation Meaning

Values that can

be displayed

Unit

Reset

possible

1

STRKS

Stroke number (Strokes)

0 ... 4.29E9

-

X

2

CHDIR

Changes of direction (Changes of Direction)

0 ... 4.29E9

-

X

3

CNT

Number of fault messages ( Counter)

0 ... 4.29E9

-

X

4

A1CNT

Number of alarms 1 (Alarm 1 Counter)

0 ... 4.29E9

-

X

5

A2CNT

Number of alarms 2 (Alarm 2 Counter)

0 ... 4.29E9

-

X

6

HOURS

Operating hours (Hours)

0 ... 4.29E9

Hours

-

7

WAY

Determined actuator travel (Way)

0 ... 130

mm or °

-

8

TUP

Actuating time up (Travel Time Up)

0 ... 1000

s

-

9

TDOWN

Actuating time down (Travel Time Down)

0 ... 1000

s

-

10

LEAK

Leakage (Leakage)

P 0.0 ... 100.0

%

-

11

PST

Monitoring of the partial stroke test

OFF / ###.#, fdini,

notSt, SdtSt,

fdtSt, notd, Strt

s for ###.#

-

12

PRPST

Time since the last Partial-Stroke-Test

###, notSt, Sdtst,

fdtSt

Days

-

13

NXPST

Time until the next Partial-Stroke-Test

###, notSt, SdtSt,

fdtSt

Days

-

14

DEVI

General control valve fault

OFF, 0.0 ... 100.0 %

-

15

ONLK

Pneumatic leakage

OFF, 0.0 ... 100.0 -

-

16

STIC

Static friction/Slipstick effect

OFF, 0.0 ... 100.0 %

-

17

ZERO

Zero point displacement

OFF, 0.0 .. 100.0 %

-

18

OPEN

Displacement of upper end stop

OFF, 0.0 ... 100.0 %

-

19

PAVG

Position average

0.0 ... 100.0

%

-

20

P0

Potentiometer value of lower end stop (0%)

0.0 ... 100.0

%

-

21

P100

Potentiometer value of upper end stop (100%)

0.0 ... 100.0

%

-

22

IMPUP

lmpulse length up (Impuls Length Up)

2 ... 160

ms

-

23

IMPDN

Impulse length down (Impuls Length Down)

2 ... 160

ms

-

24

DBUP

Dead zone up (Dead Band Up)

0.1 ... 10.0

%

-

25

DBDN

Dead zone down (Dead Band Down)

0.1 ... 10.0

%

-

26

SSUP

Slow step zone up (Short Step Zone Up)

0.1 ... 100.0

%

-

27

SSDN

Slow step zone down (Short Step Zone Down)

0.1 ... 100.0

%

-

28

TEMP

Current temperature

-40 ... 85

°C

-

29

TMIN

Minimum temperature ("min/max pointer")

-40 ... 85

°C

-

30

TMAX

Maximum temperature ("min/max pointer")

-40 ... 85

°C

-

31

T1

Number of operating hours in temperature range 1

0 ... 4.29E9

Hours

-

32

T2

Number of operating hours in temperature range 2

0 ... 4.29E9

Hours

-

33

T3

Number of operating hours in temperature range 3

0 ... 4.29E9

Hours

-

34

T4

Number of operating hours in temperature range 4

0 ... 4.29E9

Hours

-

35

T5

Number of operating hours in temperature range 5

0 ... 4.29E9

Hours

-

36

T6

Number of operating hours in temperature range 6

0 ... 4.29E9

Hours

-

Overview of Diagnostics Values