Series 6A Operation & Maintenance – Installable Options

6A O & M : 22

31
32

41
42

51
52

max. DC 8,2 V

Umax. DC 30 V

Umax. DC 30 V

Imax 100 mA

Imax 100 mA

Mechanical limit switch
module 6DR4004-6K

Fault message

Limit value A1

Limit value A2

2K1

10K

Intrinsically safe
switching amplifier
to DIN EN 60947-5-6

Non Hazardous Area

Hazardous Area, Zone 1

EEx

=

=

+

+

+

Connect the mechanical limit switch module as follows:

1. Loosen the screw on the transparent cover
2. Pull the transparent cover up to the front end stop.
3. Tighten every cable in the corresponding terminal.

NotICe

Verify the electrical specifications for these terminals based on

the wiring diagram. Do not use the non Ex board in a hazard-

ous environment.

4. Slide the transparent cover up to the end stop of the

motherboard.

5. Tighten the screw on the transparent cover
6. Connect the cables of each switch to the lug of the printed cir-

cuit board in pairs. Use the provided cable tie for this purpose.

Installing the Alarm Module

Alarm Unit

Function
The alarm unit triggers fault messages and alarms using binary

outputs. The message function is based on the change in the sig-

nal status:
If the signal status is “HIGH”, there is no alarm message and the

binary inputs are conductive.
If the signal status is “LOW”, the module reports an alarm by

shutting down binary outputs using a high-resistance.
Due to the dynamic control, this module can report the arising

operational faults automatically. Set parameters 44 to 51 to acti-

vate and parameterize the output of alarms and fault messages.

Apart from binary outputs, the alarm unit has a double-acting

binary input BE2. Depending on the selected parameters, it is used

to block or to move the actuator it to its end position. Configure

the suitable settings on parameter 43.
Device features
The alarm unit has the following features:
Available in two versions.

• Explosion-proof version for connecting to a switching

amplifier in conformity with EN 60947-5-6.

• Non-explosion-proof version for connecting to power sources

having a maximum of 35 V.

Three binary outputs. Binary inputs are potentially isolated from

the standard controller and from each other. The binary input has

dual functionality. Both inputs are implemented as logical OR

combination.

• Isolated for voltage level
• Not isolated for dry contacts

Figure 11 - Mechanical limit switch module 6DR4004-6K, EEx i