Series 6A Operation & Maintenance – Installable Options

6A O & M : 23

Proceed as follows to install the alarm unit:

1. Perform Step A to remove the module cover
2. Slide the alarm unit below the motherboard in the module

rack. Ensure that you slide it up to the end stop.

3. Connect the module to the motherboard. For this purpose, use

the 8-pole flat ribbon cable provided.

4. Refer to Figures 12 and 13 to connect the Alarm unit in stan-

dard and intrinsically safe applications

11
12

21
22

31
32

41
42

51
52

≤ 30 V

35 V

35 V

35 V

Alarm module
6DR4004-8A

+

+

+

+

Digital input 2

1K

1K

1K

+ 3 V

≥ 1

Fault message

Limit value A1

Limit value A2

#

#

#

#

11
12

21
22

31
32

≤ 25,2 V

8,2 V

8,2 V

8,2 V

Fault message

Limit value A1

Limit value A2

Alarm module
6DR4004-6A

Digital
input 2

Intrinsically safe
switching
amplifier to DIN
EN 60947-5-6

Non-hazardous area

Hazardous area, zone 1 or zone 2

EEx

EEx

EEx

EEx

+

+

+

+

+ 3 V

41
42

51
52

1

2K1

10K

2K1

10K

2K1

10K

#

#

#

#

Installing the Slotted Initiator Alarm Unit

Slotted Initiator Alarm Unit

Function
If the standard controller requires electrically independent limit

value messages, the slotted initiator alarm unit is used instead of

the standard alarm unit.
A binary output is used to display a collective fault message.

Compare with the function of the alarm unit. The floating binary

output is implemented as an automatic fault indicating semicon-

ductor output.
The other two binary outputs are used for the message of two

limits L1 and L2 which can be adjusted mechanically using slotted

initiators. Both these binary outputs are electrically independent

from the remaining electronic unit.
Device features
The slotted initiator alarm unit, abbreviated as SIA unit consists

of three binary outputs.
Proceed as follows to install the SIA unit:

1. Perform Step A to remove the module cover
2. Unscrew both the screws on the motherboard.
3. Disengage the motherboard by carefully bending the four

brackets.

4. Insert the SIA unit from the top up to the upper printed circuit

board guide of the module rack.

5. Slide the SIA unit in the printed circuit board of the module

rack approximately

1

/

8

" to the right.

6. Screw in the special screw through the SIA unit into the posi-

tioner shaft. Tighten the special screw with a torque of 17.7

in-lbs.

Figure 12 - Alarm unit 6DR4004-8A, not Ex

Figure 13

- Alarm unit 6DR4004-6A, EEx i