Series 6A Operation & Maintenance – Technical Data

6A O & M : 37

2 Optional Models

Technical specifications

1)

Only in conjunction with the basic device 6DR5...-.E.... Only T4 permissible when using with I

y

module.

Add-on modules

Without Ex protection/

with Ex d protection

With Ex ia/ib protection

With Ex n/dust protection

Ex protection acc. to ATEX

II 2G Ex ia/ib II C T4/T5/T6

1)

Ex n

II 3 G Ex nA nL[nL] IIC T6
Dust

II 3 D Ex tD A22 IP66 T100°C

Mounting location

Zone 1

Zone 2/22

Permissible ambient temperature for opera-

tion
(For devices with Ex protection: Only in con-

junction with the basic device 6DR5... -.E....

Only T4 permissible when using I

y

module.)

-30 ... +80 °C (-22 ... +176 °F)

T4: -30 ... +80 °C (T4: -22 ... +176 °F)

T5: -30 ... +65 °C (-22 ... +149 °F)
T6: -30 ... +50 °C (-22 ... +122 °F)

Alarm unit

6DR4004-8A

Binary alarm outputs A1, A2 and alarm output
• Signal status High (not responded)

Signal status Low* (responded)

(* Low is also the status when the basic

device is faulty or has no electric power

supply)

Conductive, R = 1 kΩ, +3/1 %*

Disabled, I

R

< 60 µA

≥ 2.1 mA

≤ 1.2 mA

(* When used in the flameproof

enclosure the current consump-

tion must be limited to 10 mA

per output.)

(Switching threshold with supply to EN 60947-5-6: U

H

= 8.2 V,

R

i

= 1 kΩ)

• Internal capacitance C

i

5.2 nF

5.2 nF (at "nL")

• Internal inductance L

i

Negligible

• Power supply U

H

≤ 35 V

• Connecting to circuits with the following

peak values

Intrinsically safe switching

amplifier to EN 60947-5-6
U

i

= 15.5 V DC

I

i

= 25 mA

P

i

= 64 mW

at "nA" and "tD":

U

n

= 15.5 V DC

at "nL":

U

i

= 15.5 V DC

I

i

= 25 mA

Binary input BE2
• Electrically connected to the basic device

- Signal status 0

Floating contact, open

Floating contact, closed

3 V, 5 mA

≤ 4.5 V or open

≥ 13 V

≥ 25 kΩ

- Signal status 1
- Contact load

• Electrically isolated from the basic device

- Signal status 0
- Signal status 1
- Natural resistance

• Static destruction limit

± 35 V

• Internal inductance and capacitance

Negligible

• Connecting to circuits with the following

peak values

Intrinsically safe U

i

= 25.2 V

at "nA" and "tD":

U

n

= 25.2 V DC

at "nL":

U

i

= 25.2 V DC

Electrical isolation

The 3 outputs, the input BE2 and the basic device are electrically isolated from each other

Test voltage

840 V DC, 1 s