Series 6A Operation & Maintenance – Troubleshooting

6A O & M : 26

TrOubleShOOTInG

During operation of the positioner, a few important values and parameters are continually monitored. In configuration mode, you can

configure that monitoring so that the fault message output will be activated if, for instance, a limit is exceeded. Information about what

events can activate the fault message output can be found in Figure 16

Fault

See Table #:

In which mode does a fault occur?

Initialization

1

Manual and automatic modes

2, 3, 4, 5

In which environment and under which boundary conditions does a fault occur?

Wet environment (e.g. strong rain or constant condensation)

2

Vibrating (oscillating) control valves

2, 5

Impact or shock loads (e.g. vapor shocks or breakaway valves)

5

Moist (wet) compressed air

2

Dirty (contaminated with solid particles) compressed air

2, 3

When does a fault occur?

Regularly (reproducible)

1, 2, 3, 4

Sporadically (not reproducible)

5

Mostly after a specific operation time

2, 3, 5

In automatic and manual mode, when the fault message output triggers the digital display shows what fault triggered the message.

The two digits on the lower left show the corresponding error code. If multiple triggers occur at the same time, they are displayed one

after the other cyclically. The device status, including all fault messages, can be called up using command “#48” over HART. For other

protocols please refer to their specific guide on

www.bray.com

.

You can use the advance diagnostics parameters to display fault messages in one, two or three stages. The three stage method uses

“traffic light signaling” symbolizing the type of fault occurring. The user will see either a green, yellow, or red wrench on their HMI in

relation to the S6A. Green indicates a need for maintenance, yellow an urgent need for maintenance and red indicates imminent danger

of unit failure or general failure. In addition to the fault message output, alarm outputs 1 and 2 are then used. For this purpose, set the

“XDIAG” parameter as described in Figure 17.

Settings of XDIAG Message due to

OFF

Advanced diagnostics not activated

On 1

Fault message output for threshold 3 fault

messages (one-stage)

On 2

Fault message output for threshold 3 fault

messages and alarm output 2 for threshold

2 fault messages (two-stage)

On 3

Fault message output for threshold 3 fault

messages and alarm output 2 for threshold

2 fault messages and alarm output 1 for

threshold 1 fault messages (three-stage)

When a fault occurs an error code will show up on the lower left hand corner of the screen. Remedial Measures Tables 1-5 respectively,

show possible causes of the fault messages, events which activate the fault message output or alarm outputs, settings of parameters

needed for event monitoring, and remedial measures to cancel a fault message.

Figure 16

-

Fault Messages

Figure 17

XDIAG Parameters