Series 6A Operation & Maintenance – field Connections

6A O & M : 9

Restrictors
The S6A is equipped with air restrictors to reduce the air output to

achieve actuating times of T > 1.5 s for small actuators. Restrictors

1 and 2 are used for this purpose.
Tools Needed:

• Hexagon socket 2.5 mm

Refer to Figure 3.
When turned clockwise, they reduce the air output and finally shut

it off.
In order to set the restrictors, it is recommended to close them and

then open them slowly.
In case of double-acting actuators, ensure that both restrictors

have approximately the same setting.

1

2

3

Figure 3

-

Air Restrictor

Restrictor for Y1

Restrictor for Y2, only in the version for double-acting

actuators

Hexagon socket-head screw 2.5 mm

Purging
The S6A is equipped with a purge air switch that allows the

actuator to purge air either inside of the unit or directly outside.

When the enclosure is open, the purge air switch above the

pneumatic terminal strip on the pneumatic block can be accessed.
Tools Needed:

• Instrument Screwdriver

Refer to Figure 4.
In the IN position, the enclosure is flushed from inside with a

small volume of clean and dry instrument air.
In the OUT position, the purge air is directed towards outside of

the unit.

Figure 4

- Purge Air Switch

Purge Air Switch

Pneumatic Block