Technical data, Series 6a operation & maintenance – technical data, 6a o & m : 30 – Bray 6A Series O&M Manual User Manual

Page 30: 1 basic units

Advertising
background image

All information herein is proprietary and confidential and may not be copied or reproduced without the expressed written consent of BRAY INTERNATIONAL, Inc.

The technical data herein is for general information only. Product suitability should be based solely upon customer’s detailed knowledge and experience with their application.

Series 6A Operation & Maintenance – Technical Data

6A O & M : 30

TeChnICAl DATA

1 Basic Units

3-/4-wire device (terminals 2/4 and

6/8) (6DR52.. and 6DR53..)
• Power supply U

H

18 ... 35 V DC

18 ... 30 V DC

• Current consumption I

H

(U

H

- 7.5 V)/2,4 kΩ [mA]

• Internal capacitance C

i

22 nF

22 nF (at "nL")

• Internal inductance L

i

0.12 mH

0.12 mH (at "nL")

• For connection to circuits with the

following peak values

intrinsically safe

U

i

= 30 V DC

I

i

= 100 mA

P

i

= 1 W

at "nA" and "tD":

U

n

= 30 V DC

I

n

= 100 mA

at "nL":

U

i

= 30 V DC

I

i

= 100 mA

Current input I

W

Rated signal range

0/4 ... 20 mA

Load voltage at 20 mA

≤ 0.2 V (corresponds to 10 Ω)

≤ 1 V (corresponds to 50 Ω)

Internal capacitance Ci

22 nF

22 nF (at "nL")

Internal inductance Li

0.12 mH

0.12 mH (at "nL")

For connection to circuits with the

following peak values

intrinsically safe

U

i

= 30 V DC

I

i

= 100 mA

P

i

= 1 W

at "nA" and "tD":

U

n

= 30 V DC

I

n

= 100 mA

at "nL":

U

i

= 30 V DC

I

i

= 100 mA

Electrical isolation

between U

H

and I

W

between U

H

and I

W

(2 intrinsically safe cir-

cuits)

between U

H

and I

W

Test voltage

840 V DC, (1 s)

Connections
• Electrical

Screw terminals 2.5

AWG28-12
Cable gland M20x1.5 or

½-14 NPT

Screw terminals 2.5

AWG28-12
Ex d certified cable gland

M20x1.5, ½-14 NPT or

M25x1.5

Screw terminals 2.5 AWG28-12

Cable gland M20x1.5 or ½-14 NPT

• Pneumatic

Female thread G1/4 EN ISO 228-1 or

¼ -18 NPT

External position sensor (potentiome-

ter or NCS; as option) with the follow-

ing peak values
• U

o

5 V

• I

o

(static)

75 mA

• I

s

(short-time)

160 mA

• P

o

120 mW

Maximum permissible external

capacitance C

o

1 μF

Maximum permissible external

inductance L

o

1 mH

SIPART PS2

Basic device

without Ex protection

Basic device

with Ex d protection

(flameproof enclosure)

Basic device

with Ex ia/ib protection

Basic device

with Ex n/

dust protection

Technical specifications

Advertising