Notice – Bray 6A Series O&M Manual User Manual

Page 21

Advertising
background image

All information herein is proprietary and confidential and may not be copied or reproduced without the expressed written consent of BRAY INTERNATIONAL, Inc.

The technical data herein is for general information only. Product suitability should be based solely upon customer’s detailed knowledge and experience with their application.

Series 6A Operation & Maintenance – Installable Options

6A O & M : 21

Installing the Mechanical Limit Switch Module

Mechanical Limit Switch Module

Function
This module is used to report two limits. These two limit switches

are voltage free and rated for 4A at 24V DC or AC 250V.
Device features
The mechanical limit switch module consists of:

• One binary output to display a collective fault message.

Compare with the device features of the alarm unit.

• Two switches to report two mechanically adjustable limits.

Both of these switches are electrically independent from the

remaining electronic unit.

Note: Only qualified personnel should be allowed to install and

connect the Mechanical Limit switch module

Proceed as follows to install the mechanical limit switch module:

1. Perform Step A to remove the module cover
2. Disengage the motherboard by carefully bending the four

brackets.

3. Insert the mechanical limit switch module from the top up to

the upper printed circuit board guide of the module rack.

4. Slide the mechanical limit switch module unit into the printed

circuit board of the module rack approximately

1

/

8

" towards

the right.

5. Screw in the special screw through the mechanical limit

switch module into the positioner shaft. Tighten the special

screw with a torque of 17.7 in-lbs.

NotICe

A pin in the actuating disc bearing is pressed. Align this pin

before it touches the special screw. You must rotate the actuating

disc bearing and the special screw simultaneously so that the pin

is inserted into the special screw.

An insulating cover is provided over the mechanical limit switch

module. Place the insulating cover to one side under the mother-

board seat on the container wall. The recesses of the insulating

cover must fit in the corresponding webs of the container wall.

6. Place the insulating cover on the mechanical limit switch

module by bending the container walls carefully.

7. Engage the motherboard into the four brackets.
8. Connect the motherboard and the optional modules to the

ribbon cables provided.

9. Connect the motherboard and the potentiometer to the

potentiometer cable.

10. Using both the screws, fasten the module cover provided.
Do not use the standard module cover.
11. Refer to Figures 10 and 11 to connect the Mechanical Limit

switch module in standard and intrinsically safe applications.

31
32

41
42

51
52

<35 V

24 V DC

max. AC 250V

4A AC/DC

24 V DC

max. AC 250V

4A AC/DC

1K21

10K

Fault message

Limit value A1

Limit value A2

+

+

+

Mechanical limit switch
module 6DR4004-8K

Figure 10 - Mechanical limit switch module 6DR4004-8K, not Ex

Advertising