All information herein is proprietary and confidential and may not be copied or reproduced without the expressed written consent of BRAY INTERNATIONAL, Inc.

The technical data herein is for general information only. Product suitability should be based solely upon customer’s detailed knowledge and experience with their application.

Series 6A Operation & Maintenance – Calibration & Commissioning

6A O & M : 16

Parameter

Function

Parameter Values

Description

Turn

Automatically sets 2) YAGL to 90

WAY

Used for linear actuators

LWAY

Used for linear actuators

ncSt

Used for a non-contacting position sensor on a part

turn actuator

-ncSt

Used for a non-contacting position sensor on a part

turn actuator with a reverse direction of action

ncSL

Used for linear actuators

1) YFCT

Type of position actuator

ncSLL

Used for linear actuators

33

2) YAGL

Angle of rotation

90

Used for linear actuators

3) YWAY

Range of Stroke

Used for linear actuators

4) INITA

Initialization (automatic)

NOINI | no/ ###.# | Strt

Starts the automatic initialization process

5) INITM

Initialization (manual)

NOINI | no/ ###.# | Strt

Starts the manual initialization process

0 MA

0 MA only available for 3 to 4 wire connections.

6) SCUR

Current range of setpoint

4 MA

Factory setting.

riSE

7) SDIR

Setpoint Setup

FALL

Used to reverse the direction of the action of the

setpoint. Factory setting is “rise”

8) SPRA

Setpoint split range start 0.0 … 100.0

Used to limit the setpoint. Factory setting is “0”

9) SPRE

Setpoint split range end

0.0 … 100.0

Factory setting is “100”

10) TSUP

Setpoint ramp OPEN

Auto / 0 … 400

11) TSDO

Setpoint ramp CLOSED

0 … 400

Limits the speed of change of the effective setpoint.

Factory setting is “0”

1 – 25

1 – 33

1 – 50

Equal Percentage. Linearizes valve characteristics.

Factory setting is “Lin”

n1 – 25

n1 – 33

n1 – 50

Inverse equal percentage

12) SFCT

Setpoint Function

FrEE

Freely Adjustable

13) SLO

33) SL20

Setpoint Turning Point

0.0 … 100.0

Assigns a flow metric to each setpoint interpolation

in units of 5%.

34) DEBA

Dead Zone of Closed-

Loop Controller

Auto / .1 … 10.0

Adjust the dead zone to the requirements of the

control loop. Factory setting is “Auto”

35) YA

Start of the manipulated

variable limit

0.0 … 100.0

36) YE

End of the manipulated

variable limit

0.0 … 100.0

Used to limit the mechanical actuator travel from

stop to stop to the configured values. “YE” must

always be larger than “YA”. Factory setting is “100”

MPOS

Mechanical position from 0 to 100% between hard

stops.

37) YNRM

Manipulated variable

scaling

FLOW

Scaling from 0 to 100% over the range between

“YA” and “YE”

riSE

38) YDIR

Direction of Manipulated

Variable

FALL

Used to set the direction of action of the display and

the position feedback Iy. Factory setting is “riSE”

No

uP

Do

39) YCLS

Manipulated variable tight

closing

uP do

Used to move the valve into its seat with the

maximum force of the actuator. Factory setting is

“No”

40) YCDO

Lower value for tight

closing

0.0 … 0.5 … 100%

Factory setting is “0.5”