Series 6A Operation & Maintenance – Calibration & Commissioning

6A O & M : 17

41) YCUP

Upper value for tight

closing

0.0 … 99.5 … 100%

Used to set the value for tight “Tight closing below”

and “Tight closing above”. Factory setting is “99.5”

Normally

Open

Normally

Closed

Functions while in binary input mode.

OFF

Factory setting.

on

-on

Binary message from peripherals

bloc1

Used to lock the configuration operation

bloc2

uP

-uP

doWn

-doWn

Actuator regulating to the valve specified by

parameters “YA” and “YE”

StoP

-StoP

Piezo valves are blocked. Actuator remains at last

position.

42) BIN1 2) Function of BE1

PST

-PST

Used to trigger a partial stroke test

Normally

Open

Normally

Closed

Functions while in binary input mode.

OFF

Factory setting.

on

-on

Binary message from peripherals

uP

-uP

doWn

-doWn

Actuator regulating to the valve specified by

parameters “YA” and “YE”

StoP

-StoP

Piezo valves are blocked. Actuator remains at last

position.

43) BIN2 2) Function of BE2

PST

-PST

Used to trigger a partial stroke test

Normal

Inverted

Off

44) AFCT 3) Alarm Function

Used to determine the value at which going above or

below a given offset or angle will result in a

message.

45) A1

Trigger threshold, alarm 1

0.0 … 10.0 … 100 %

46) A2

Trigger threshold, alarm 2

0.0 … 90.0 …100%

Used to specify when an alarm should be displayed.

Normal

Inverted

47) FCT 3)

Function for fault

message output

Cannot be switched off. Can be suppressed by

switching to “No Automatic Mode”

48) TIM

Monitoring time for

setting of fault message

Auto / 0 … 100

Used to set the time in seconds that the positioner

must have reached the regulated condition.

49) LIM

Response threshold for

fault message

Auto / 0 … 100

Used to set a value for the permissible size of the

regulation device to trigger a fault message.

no

Strt

50) PRST

Preset (factory setting)

oCAY

Used to restore factory settings and reset

initialization. Press increment button for 5 seconds.

OFF

On1

On2

51) XDIAG

Activation of extended

diagnostics

On3

Used to activate extended diagnostics.

FSVL

Actuator controlled using the parameterization safety

point. Effective after a power failure.

FSSP

Actuator controlled using the last effective set point

52) FSTY

Safety Seating

FSAC

Valves move to location based on spring force.

(Factory Defined)