Bray 6A Series O&M Manual User Manual

Page 28

Advertising
background image

All information herein is proprietary and confidential and may not be copied or reproduced without the expressed written consent of BRAY INTERNATIONAL, Inc.

The technical data herein is for general information only. Product suitability should be based solely upon customer’s detailed knowledge and experience with their application.

Series 6A Operation & Maintenance – Troubleshooting

6A O & M : 28

Fault profile (symptoms) Possible cause(s)

Remedial measures

In stationary automatic mode

(constant setpoint) and in manual

mode, both piezo valves contin-

ually switch alternately, and the

actuator oscillates around a mean

value.

Sticking friction of the packing gland from the

control valve or actuator too large

Reduce friction or increase dead zone of positioner (param-

eter ”dEbA”) until the oscillation stops

Looseness (play) in the positioner/actuator/con-

trol valve system

Part-turn actuator: Check for firm seating of set screw on cou-

pling wheel
Linear actuator: Check for firm seating of lever on positioner

shaft
Correct any other play between the actuator and the control

valve

Actuator is too fast

Positioner doesn’t move control

valve to the stop (at 20 mA)

Supply pressure too low. Load on the feeding

controller or system output is too low

Increase supply pressure, insert ballast converter
Select 3/4-wire mode

Remedial Measures Table 4

Remedial Measures Table 5

Fault profile (symptoms) Possible cause(s)

Remedial measures

Zero point displaces sporadi-

cally (> 3%).

Impact or shock loads result in accelerations

so high that the friction clutch moves, e.g.

due to ”vapor shocks” in vapor lines

Rectify the causes for shock loads
Re-initialize the positioner

The device function has com-

pletely failed: no view even

on the digital display.

Electrical auxiliary power supply is not

adequate

Check the electrical auxiliary power supply

In case of very high continuous loads due to

vibrations (oscillations):
Screws of the electrical connecting terminals

may be loose
Electrical connecting terminals and/or elec-

tronic components may be knocked out

Tighten the screws firmly x
Repair

1)

For prevention: install the positioner on the damping pads

Advertising