Installing the EMC Filter Module

EMC Module

Function
You will require the EMC filter module if you use an external

position sensor on the positioner, e.g. a potentiometer or a non-

contacting position sensor. The EMC filter module forms the

interface between external position sensors and the motherboard

of the positioner. This module protects the positioner from elec-

tromagnetic effects.
Device features include:

• EMC protection
• Connection to motherboard
• Connecting terminals for an external potentiometer

Proceed as follows to install the EMC filter module:
1. Perform Step A to remove the module cover
2. Remove the module cover.
3. Dismantle all existing optional modules.
4. Unscrew the screws of the module rack that are opposite to

the blanking plugs.

5. The EMC filter module has a fastening hole. Tighten the

module on the module rack using the screws provided

6. Lay the ribbon cable of the EMC filter module towards left

through the opening of the module rack.

7. Unplug the connector of the internal potentiometer from the

motherboard.

8. Connect the ribbon cable of the EMC module to the

motherboard.

9. Connect the external position sensor to the terminals of the

EMC module.

10. Reinstall the other optional modules in the reverse order.
11. Refer to Figures 14 and 15

to reconnect the SIA module in

standard and intrinsically safe applications

12. Install the module cover.