Fitting the position feedback with stroke, Limiter to a pneumatic actuator size 100 or 125mm – Burkert Type 1062 User Manual

Page 23

Advertising
background image

23

Assembly

Type 1062

7.5

fitting the position feedback with
stroke limiter to a pneumatic
actuator size 100 or 125mm

note

the tightness of the actuator is not guaranteed when the
transparent cap is removed.

▶ Prevent the projection of fluids into the actuator.
the tightness of the position feedback is not guaranteed
when the cover is removed.

▶ Prevent the projection of fluids into the position feedback.
the position feedback may be damaged if a metal com-
ponent comes into contact with the electronics.

▶ Prevent contact of the electronics with a metal component (a

screwdriver, for example).

C
D

Unscrew the cone point set
screw "C" from the 1062 to
unlock the duplication system "D"
using a hexagonal male spanner.

Carefully remove the duplication
system "D" from the housing of
the 1062.

E

Check that the seals have
been fitted and that they are
undamaged. Replace them if
necessary.

Put thread lock into the internal
thread in the duplication rod "E".

F

G

Unscrew the small transparent
cap "F" on the actuator, pre-
ferably by hand or using a sui-
table tool in order not to damage
it

Pump air into the actuator on a
valve which is normally closed
(function "A") or has a double
effect (function "I") so that the
actuator rod moves to the top
position.

Unscrew the visual position
feedback "G" using a hexagonal
male spanner.

english

Advertising
This manual is related to the following products: