Installationandwiring

Type 1062

C
D

Insert the position feedback
housing into the duplication
system "D" setting the
cable gland in the direction
desired and making sure, on
a mechanical contact version,
that you do not damage the
contact levers on the switches.

Fasten the housing and the
duplication system by tight-
ening the cone point set screw
"C" using a hexagonal male
spanner.

R

S

Unscrew the cover "R" on the
position feedback.

Unscrew the cable gland "S".

Thread the cable through the
cable gland.

Wire according to the wiring
diagram for your version of the
1062: See chap. „8 Installation
and wiring“.

Fasten the cable gland to
ensure tightness of the product.

8

insTAllATion AnD WiRinG

8.1

safety instructions

Risk of explosion.
When the 1062 is used in an ATEX 21 or 22 zone, make sure:
• That the cover of the electrical position feedback is always

screwed shut before operating the valve.

• That you check that the device is not subject to a flow of air and

dust that may result in an accumulation of electrostatic charges.
Otherwise, intall the device in a conductive cover.

• "The NAMUR switches on the 1062 must be powered by a voltage

source of a type certified for use in explosive atmospheres in
groups IIB/IIC and their combination must be compatible from the
instrinsic safety point of view."