Corrected Liquid Volume

121-000-350 © 2001 Max Machinery, Inc.

Pg 11

3.2 Corrected Liquid Volume

Measurements:

A flowmeter measures the actual volume in a liquid line. A temperature sensor is installed to correct for liquid

thermal expansion.

Calculations:

• Corrected Volume is calculated using the flow and temperature inputs as well as the thermal expansion

coefficient stored in the flow computer. Use the "SET FLUID PROPERTIES" submenu to define reference
temperature and density values for standard conditions.

Output Results:

• Display Results

Flow Rate, Resettable Total, Non-Resettable Total, Temperature, Density

• Analog Output

Rate, Total, Temperature or Density

• Pulse Output

Total

• Relay Outputs

Rate , Total or Temperature Alarms

Applications:

Monitoring corrected volume flow and total of any liquid. Flow alarms are provided via relays and datalogging
is available via analog (4-20mA) and serial outputs.

Corrected
Liquid Volume
Illustration

Volume Flow

As calculated in section 3.1

Corrected Volume Flow (Temp. Transmitter)

Corrected Volume Flow = vol. flow • (1 - Therm.Exp.Coef. • (Tf-Tref))

2

Calculations

Temp./Dens.

Transmitter