Installation, 121 series, Dimensions – Max Machinery 121 INDICATOR User Manual

Page 9

Advertising
background image

121 Series

121 Series

Bezel Adaptor

Gasket

Mounting Bracket

Mounting Bracket

Dimensions

Dotted Line Shows Optional Bezel Kit

Panel

Cutout

5.43

(138)

2.68

(68)

5.67 (144)

2.83

(72)

3.43

(87)

6.18

STOP

START

PRINT

5

0

TIME

CLEAR

MENU

ENTER

HELP

TEMP

4

PRE 1

3

RATE

2

TOTAL

1

GRAND

6

SCROLL

7

PRE 2

8

DENS

9

RATE
TOTAL 267395.749

GPM
GAL

147.43

6.15

(156)

0.5

(13)

0.28 (7.2)

0.4 (10)

2.1 General Mounting Hints:

The 121 Series Flow Computer should be located in an area with a clean, dry
atmosphere which is relatively free of shock and vibration. The unit is installed in a
5.43" (138mm) wide by 2.68" (68mm) high panel cutout. (see Mounting Dimensions)
To mount the Flow Computer, proceed as follows:

Mounting Procedure:

a. Prepare the panel opening.
b. Slide the unit through the bezel adaptor and gasket.
c. Push the unit through the panel cutout until it touches the panel.
d. Install the screws (provided) in the mounting bracket and slip the bracket over
the rear of the case until it snaps in place.
e. Tighten the screws firmly to seat the bezel against the panel.

Termination Connectors:

Minimum Wire Gauge: 22 AWG
Maximum Wire Gauge: 14 AWG
Voltage/current limits are limited by unit specifications.

Permanently Connected Equipment:
UL 3101-1, Section 6.12.2.1 specifies that:

• A switch or circuit breaker shall be included in the building installation;
• It shall be in close proximity to the equipment and within easy reach of the
OPERATOR;
• It shall be marked as the disconnecting device for the equipment.

Ensure that the switch or circuit breaker chosen is suitable for the power
requirements of the unit.

2.2 Mounting Diagrams:

Installation

121-000-350 © 2001 Max Machinery, Inc.

Pg 9