13.2 Diagnosis Flow Chart and Troubleshooting

13.3.2
Self Test Alarms

Error/Warning Message

FLOW INPUT TOO HIGH

AUX INPUT TOO HIGH

FLOW INPUT TOO LOW

BATTERY LOW WARNING

A to D NOT CONVERTING

TIME CLOCK ERROR

CAL CHECKSUM ERROR

SETUP CHECKSUM
ERROR

Cause

Analog input signal of the
flow input exceeded by
more than 3%:
• Sensor overranged
• Incorrect full scale setting
of flowmeter
• Function error in transmit-
ter or faulty wiring

Analog input signal of the
auxiliary input exceeded by
more than 3%:
• Sensor overranged
• Incorrect full scale setting
of transmitter
• Function error in transmit-
ter or faulty wiring

Analog input signal of the
flow input fell below the low
scale range by more than
3% of full scale value:
• Flowmeter not set to 4-20
mA
• Function error in transmit-
ter or faulty wiring

Battery voltage too low

Fault in analog/digital con-
verter

The correct time/date is no
longer shown

Calibration constants have
been corrupted

The units setup has been
corrupted

Remedy

• Check analog signal range
• Check the application con-
ditions
• Check wiring

• Check analog signal range
• Check the application con-
ditions
• Check wiring

• Check wiring
• Check calibration of
flowmeter
• Check function of flowmeter

• Replace Battery
• Consult Factory for service
information

• Unit may self correct,
Press ENTER to acknowl-
edge & clear alarm
• If error reasserts, factory
service is required

• Re-enter time and date.
• If error occurs again con-
tact factory

• Report error to factory

• Report error to factory