121-000-350 © 2001 Max Machinery, Inc.

Pg 31

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

ENTER

6.4.14
SETUP
ANALOG OUTPUT

6.4.15
SETUP RELAYS
(Relay 1 & Relay 2)

NOTE:

In Batch mode, Relay 1
is reserved for Preset,
Relay 2 is reserved for
Prewarn.

SETUPANALOG OUTPUT

ANALOG OUTPUT U S A G E
Rate Total Temp Dens

ANALOG OUTFLOW T Y P E
Vol CVol/Mass

ANALOG OUTPUT R A N G E
4-20mA

0-20mA

LS ANALOG OUTPUT

####### gal/m

FS ANALOG OUT 20mA
####### gal/m

ANALOG OUT DAMPING

0.0

Advance To

SETUP RELAYS

SETUP RELAYS

Rly1 Rly2

Rly3 Rly4

RELAY 1 USAGE
RATE TOTAL

NA

RELAY 1 DELAY

sec

0

RELAY 1 MODE
LO_ALARM HI_ALARM

RELAY 1 DURATION
#####

RELAY 1 SETPOINT
####### gal

RELAY 1 HYSTERESIS
##### gal/m

Press ENTER when Analog is flashing to setup the
Analog Output.

Select the desired Analog Output Usage.

Only if Rate selected & Flow EQ. = Mass, Cor/Vol
Select the desired Analog Output Flow.

Select the desired current range for the Analog Output.

Enter desired Analog Output Low Scale Value.
NOTE: Units label will correspond with output usage

type selected.

Enter desired Analog Output Full Scale Value.

Enter the desired Analog Output Damping Constant.

Select the desired Relay for setup.
(Relays 3 & 4 Optional)

If Relay 1 or Relay 2 Selected,
Select Rate, Total or NA.

If Rate selected, enter desired relay activation delay
value.

Select the desired Relay Activation.
Low:

Relay activates when reading is below setpoint.

High:

Relay activates when reading is above setpoint.

If Total Selected, Enter desired Relay Duration.

Enter the desired Setpoint. The Setpoint can be edited in
run mode using the PRE 1 key (PRE 2 key for Relay 2).

If Rate, selected, Enter desired Relay Hysteresis.