OUTSTANDING ALARM MESSAGES

ALARM
MESSAGE

Explanation

AC INPUT FAIL

Meaning: The voltage of one or more of the input AC phases is out of
range, or there is no AC input at all. The UPS is now in Battery Mode.

Additional indications: The alarm LED lights up and the audible alarm

sounds. The symbol

appears on the AC Input screen.

Action: If there is a power outage, it is advisable to save any critical open
files you are working on before the UPS battery is exhausted. See chapter
13, “In the event of an AC power outage”.
If there is not a power outage, check the circuit breaker for the line
supplying the UPS with power. The circuit breaker may be off.

AC OUTPUT FAULT

Meaning: The voltage of at least one of the output AC phases is out of
range.

Additional indications: The alarm LED lights up and the audible alarm

sounds. The symbol

appears on the AC Output screen.

Action: After a power outage, this message can be ignored.
This message could also be the result of an overload. Reduce the load on
the UPS; this may resolve the problem. If not, contact Gamatronic
Technical Support.

BATTERY LOW

Meaning: The battery will soon be fully discharged.

Additional indications: The alarm LED lights up and the audible alarm

sounds. The symbol

appears on the Main Screen.

Action: Shut down your computer or other equipment connected to the
UPS.

BATTERY TEST FAIL

Meaning: The most recent battery test has failed.

Additional indications: The alarm LED lights up and the audible alarm

sounds. The symbol

appears on the Main Screen.

Action: It is possible that the most recent battery test occurred after a
power outage and before the battery had fully recharged. Wait until two
hours have elapsed from the most recent battery test and perform a manual
battery test. See “Manual battery test” on page 43.

+