Bypass option activation / deactivation – MaxPower Corp Gamatronic Power+ SA User Manual

Page 60

Advertising
background image

Gamatronic Electronic Industries Ltd.

10. BYPASS OPTION ACTIVATION /

DEACTIVATION

The P

OWER

+

SA should not be operated without the bypass option except under the

supervision of a qualified technician.

Operation of the P

OWER

+

SA without a bypass source can result in damage to the

equipment (load devices) connected to the UPS. No one but a qualified technician
should be permitted to deactivate the bypass mode capability.

Before activating or deactivating the bypass option, verify the current status of the
bypass option by going to the UPS profile screen #3:

From the Main Screen, press

three times.

The current status of the bypass option is shown in the first line under the “UPS
PROFILE” header.

To deactivate the bypass option:

1.

If the P

OWER

+

SA is not already in “off” mode, press the ON/OFF button

twice to turn the UPS off.

2.

From the Main Screen, press the Ent button to display the Main Menu.

3.

On the Main Menu, choose ADVANCED OPTIONS and press Ent.

4.

In the ADVANCED MENU, select TECHNICIAN MENU.

5.

In the TECHNICIAN MENU select BYP. ACTIVATION.

6.

A warning message is displayed.

POWER+ SA User Guide (UL), Release 1.0

54

Advertising