MaxPower Corp Gamatronic Power+ SA User Manual

Page 47

Advertising
background image

Gamatronic Electronic Industries Ltd.

User Guide

ONE PHASE FAULT

Meaning:One or more of the AC phases into the Charger is out of range.

Additional indications The alarm LED lights up and the audible alarm
sounds.

Action: This is likely to be due to a problem with the input AC supply.

OVERLOAD

Meaning:There is an overload condition.

Additional indications The alarm LED lights up and the audible alarm
sounds. If the output current is between 104 – 117%, for 10 minutes, or
between 117 – 131% for one minute, or above 131% for 20 msec, the UPS

shuts down. The symbol

appears on the Main Screen.

Action: Reduce the load to the UPS quickly, or the UPS will automatically
move to Bypass mode.

+

41

POWER SA User Guide (UL), Release 1.7

Advertising