4 electrical wiring, 66 are used, 4 elect r rical wiring – MaxPower Corp Gamatronic Power+ SA User Manual

Page 72

Advertising
background image

Gamatronic Electronic Industries Ltd.

15.2.4 Elect

r

rical Wiring

1.

Verify that power wiring is run in an individual separate conduit or cable tray.
Verify that control wiring is run in an individual separate conduit.

2.

For proper conductor size refer to Table 15-1, which has been prepared in
accordance with NEC requirements. (Please check your local electrical codes to
ensure compliance with the given grades.) The values shown in Table 15-2
conform to UL requirements.

Table 15-1: Electrical ratings and external wiring requirements

RATINGS & EXTERNAL WIRING REQUIREMENTS

FOR THE POWER+ SA, 3:3 PHASE, 10kVA, 60Hz GE MODEL

Basic unit ratings at full load

kVA/kW

VOLTAGE

(Volts)

CURRENT

(Amps)

CONDUCTOR

SIZE

AC INPUT

AC Input to UPS
Full Load Current 3Ø,
(1) Neutral, (1) Gnd

-

208

28

(5) x 8AWG

AC OUTPUT

UPS AC Output
Full Load Current 3Ø,
(1) Neutral, (1) Gnd

10/8

208

28

(5) x 8AWG


Table 15-2: Required wire ratings

AC

OUTPUT

G

ND

,

N,

L1,

L2,

L3

B

YPASS INPUT

G

ND

,

N,

L1,

L2,

L3

AC

INPUT

G

ND

,

N,

L1,

L2,

L3

B

ATTERY INPUT

G

ND

,

+,

N,

-

8 AWG

8 AWG

8 AWG

8 AWG



3.

Ensure that the lines coming into the UPS are equipped with circuit breakers of
the capacity shown in Table 15-3 below.

Table 15-3: UL-required circuit breaker ratings

L

INE

C

IRCUIT BREAKER RATING

UPS output

35A

Bypass

35A

AC input

35A

POWER+ SA User Guide (UL), Release 1.0

66

Advertising