2 installing the power + sa, Installing the p, Ower – MaxPower Corp Gamatronic Power+ SA User Manual

Page 74

Advertising
background image

Gamatronic Electronic Industries Ltd.

15.3.2 Installing the P

OWER

+

SA

For 2-phase use, follow the instructions in section 20.1.1 beginning on page 85,
rather than those in this section.

Before continuing, read carefully the preceding part of this chapter beginning from
section 15.2
Site Preparations” on page 64 if you have not already done so. Pay
special attention to the safety warnings and wiring requirements.

To install the UPS and prepare it for initial start-up:

1.

Verify that the external circuit breakers in the mains electrical cabinet for UPS
input
, UPS output, and bypass are OFF. No voltage should be present in the
cables.

2.

Verify that the battery cabinet circuit breaker is OFF.

3.

Remove the protective cover from the UPS rear panel.

4.

Connect the UPS wiring according to the labeling on the unit, shown in Figure
15-3 on page 69.

Figure 15-2: UPS rear panel with protective cover

POWER+ SA User Guide (UL), Release 1.0

68

Advertising