3 modifying the output ac voltage, 1 to change the nominal output ac voltage, See “modifying the output ac voltage – MaxPower Corp Gamatronic Power+ SA User Manual

Page 56

Advertising
background image

Gamatronic Electronic Industries Ltd.

9.3

Modifying the output AC voltage

Do not change the output voltage unless you are sure that this is required by your
load devices and that the new output voltage will not damage the load devices.

Two types of adjustments can be made to the output voltage:

• The nominal AC output voltage can be changed.

• The voltage of each AC output phase can be fine-tuned.

9.3.1

To change the nominal output AC voltage:

1.

If the P

OWER

+

SA is not already in “off” mode, press the ON/OFF button

twice to turn the UPS off.

2.

From the Main Screen, press the Ent button to display the Main Menu.

3.

On the Main Menu, choose ADVANCED OPTIONS and press Ent.

4.

In the ADVANCED MENU, select TECHNICIAN MENU.

5.

In the TECHNICIAN MENU select CHANGE VOLTAGE.

6.

You are prompted to choose the type of voltage to change.
Select OUTPUT VOLTAGE.

7.

You are prompted to choose a change to the nominal value or an adjustment
(fine-tuning). Choose NOMINAL VALUE.

8.

Use the UP/DOWN button to change the output voltage. You can adjust it in a
range from 110 to 120V. Press Ent to apply the change.

POWER+ SA User Guide (UL), Release 1.0

50

Advertising