UPS Battery Unit Description

The UPS Battery Unit is subject to wear and should be replaced regularly (at least
following the specified life span).

The figure shows the UPS Battery Unit:

The table provides the technical data on the UPS Battery Unit:

Features

Values

Battery:
Type
Method

Hawker Cyclon 12 Vdc 4.5 Ah (2 connected in series)
Single cell (X cell)

Rated Voltage

24 Vdc

Operating Current

Max. 4.5 Ah

Battery Charging Current

Max. 2.88 A

Ambient Temperature:
Charging Mode
Storage and Transport

–30...60

C (–22...140 F)

–65...80

C (–85...176 F)

Relative Humidity:
Operation
Storage and Transport

5...95 %, non-condensing
5...95 %, non-condensing

Altitude

Max. 3000 meters (9843 feet)

Life Span

Up to 15 years at 25

C (77 F) (up to 80 % battery ca-

pacity)

Maintenance Interval (During Stor-
age)

Charge once every 6 months

Typical Recharge Time at Low Bat-
tery

15 hours

Weight

Approximately 5 kg (11.02 lbs)