Grounding I/O Signal Lines

Electromagnetic radiation may interfere with the control communications of the
Industrial Personal Computer.

DANGER

POTENTIAL FOR EXPLOSION

Always confirm the ANSI/ISA 12.12.01 and CSA C22.2 N

213 hazardous

location rating of your device before installing or using it in a hazardous location.

To power on or power off a Industrial Personal Computer installed in a Class I,
Division 2 hazardous location, you must either:

Use a switch located outside the hazardous environment, or

Use a switch certified for Class I, Division 1 operation inside the hazardous
area.

Do not connect or disconnect equipment unless power has been switched off or
the area is known to be non-hazardous. This applies to all connections including
power, ground, serial, parallel, network and rear USB connections.

Never use unshielded / ungrounded cables in hazardous locations.

When enclosed, keep enclosure doors and openings closed at all times to avoid
the accumulation of foreign matter inside the workstation.

Use only non-incendive front USB configurations (see page 69).

Failure to follow these instructions will result in death or serious injury.

WARNING

UNINTENDED EQUIPMENT OPERATION

If wiring of I/O lines near power lines or radio equipment is unavoidable, use
shielded cables and ground one end of the shield to the Industrial Personal
Computer ground connection screw.

Do not wire I/O lines in proximity to power cables, radio devices, or other
equipment that may cause electromagnetic interference.

Failure to follow these instructions can result in death, serious injury, or
equipment damage.