Ol2108 relay output module – Nematron Pointe Controller User Manual

Page 237

Advertising
background image

Pointe Controller User Guide

Appendix A: OptiLogic Technical Specifications

235

A.2

OL2108 Relay Output Module

The OL2108 Relay Output Module provides eight (8) optically
isolated mechanical relay outputs that can be used for
switching a variety of AC and DC loads. Individual LED
indicators provide visual feedback of output state.

Technical Specifications

Card Cage Power Required

375 mA

Output Type

Mechanical relay

Outputs

8

Status Indicators

Logic Side LED

Contact resistence

0.1 ohm (initial)

Contact voltage rating

0 - 60 VDC
0 - 120 VAC

Contact rating

2A (resistive) / point @24 VDC,
1A / point @120 VAC

Minimum load

10 mA

Contact type

Form A (SPST)

Contact arrangement

4 relays per common

Mechanical life

10,000,000 operations per relay (at no load)

Electrical life

100,000 operations per relay (at full load)

Terminal Strip

Plug In (removable)

Terminal Screws

Slotted (0.1” blade max)

Max. terminal wire gauge

18 AWG (use copper conductors)

Terminal block torque

2.2 lb-in

Required Temp. rating of
field installed conductors

60°C / 75°C

Weight

2.1 oz (58 g)

Type

9

Subtype

1

Advertising