Ol2252 dual pulse counter – Nematron Pointe Controller User Manual

Page 260

Advertising
background image

Appendix A: OptiLogic Technical Specifications

Pointe Controller User Guide

258

A.9

OL2252 Dual Pulse Counter

The OL2252 module provides two independent high
speed pulse counter inputs. Each input counter will
accurately count pulse inputs up to 15KHz. Inputs may be
sourcing or sinking type. There are a number of operating
options available with the OL2252. The six remaining
inputs can be used as predefined control signals or as
general purpose inputs. These options are detailed below.

Input Connections

The following is a list of the input connections on the module:

Terminal

Label

Description

1

Common

Sourcing or sinking return line

2

Common

Sourcing or sinking return line

3

Pulse 1

Square wave input, up to 15 KHz

4

Pulse 2

Square wave input, up to 15 KHz

5

Reset 1

If configured as “reset” input, will clear the Pulse 1 count
when activated. If not configured as “reset” input, can be
used as a general purpose input.

6

Reset 2

If configured as “reset” input, will clear the Pulse 2 count
when activated. If not configured as “reset” input, can be
used as a general purpose input.

7

Enable 1

If configured as an “enable” input, enables the Pulse 1
counter when active. If not configured as an “enable” input,
can be used as a general purpose input.

8

Enable 2

If configured as an “enable” input, enables the Pulse 2
counter when active. If not configured as an “enable” input,
can be used as a general purpose input.

9

Input 1

General purpose input

10

Input 2

General purpose input

Theory of Operation

The OL2252 Pulse Counter has two independent pulse counter inputs. These pulse
counter inputs will accurately co

unt pulses between 0 and 15KHz.

All counts begin at zero and count up to the maximum number the counter can
hold (4,294,967,295). If the count should ever get that h

igh, it will roll over to

zero.

In order to count, the count input must be enabled. A message with an enable
must come from the runtime program. The module can also be set up to use the
local hardware input enable (in addition to the enable message).