Nematron Pointe Controller User Manual

Page 271

Advertising
background image

Pointe Controller User Guide

Appendix A: OptiLogic Technical Specifications

269

To configure Input LS, click the

to the right and select a tag from the

pop-up menu. Each tag can be used only once.

NOTE: These inputs do not necessarily need to be mapped to tags in Logic
Memory for the pulse counter itself to function. The counter will still count pulses
and write out the counter value, as configured in the Counter tab (below).
However, it is sometimes useful to have access to these I/O points independent of
the counter function.

Counter tab

General configuration parameters for pulse counter.

Counter Type – The mode in which the counter will operate (see above).
Options include:

o

Pulse/Direction (default) – In this mode, pulses are counted by

Input A and the counter direction is determined by Input B.

o

Up/Down Count – In this mode, pulses received by Input A

increment the counter and pulses received by Input B
decrement the counter.

o

Quadrature – In this mode, counting is determined by the phase

angle between Input A and Input B. If A leads B, then the
counter increments. If B leads A, then the counter decrements.

To configure Counter Type, click the

to the right and select a mode

from the pop-up menu.

Frequency Selection – The frequency at which pulses will be received
and counted. Options include:

o

Up to 30 KHz – The maximum pulse frequency will be less than

or equal to 30 KHz.