Appendix C: Ladder Diagram Block Reference

377

Functional Description

This block always passes the Enable input state (EN) through to the Enable Out
output state (ENO) without change; when EN becomes on, ENO is turned on, and
when EN becomes off, ENO is turned off.

When EN becomes on, the block function is executed: the Input Value 1 (IN1) is
raised to the power of the Input Value 2 (IN2) and the result is placed in the
Output Value (OUT).

The block function is executed every time the ladder is

scanned

, so long as EN

remains on. If EN becomes off, then OUT remains at its last calculated value until
EN becomes on and the block function is executed again.

Configuration Reference

The parameters of this block are described in the following table:

Param

Name

Config

Var Type

Description

EN

Enable

no

-

The state of the rung (off/on)
received from the left.

ENO

Enable
Out

no

-

The state of the rung (off/on)
passed to the right.

IN1

Input
Value 1

req

real only*

Numeric

The base input value. If a Numeric
value is manually entered, it must
be real / floating.

IN2

Input
Value 2

req

real only*

Numeric

The exponent input value. If a
Numeric value is manually entered,
it must be real / floating.

OUT

Output
Value

req

real only*

The result of raising the base input

value to the exponent input value.

* Any 32-bit Real (F) Input, Output, or Memory tag. For more information, see “

Defining Input,

Output, Memory tags

” on page 114

.

NOTE: This function does not check for bit register overflow. If overflow occurs,
the value “1.#INF00” (infinite) is placed in the output.