Features, Ldm-32f, Introduction features 10 – Fire-Lite LDM-32F Lamp Drivers User Manual

Page 10: Figure 1 ldm-32f

Advertising
background image

1. Introduction

Features

10

LDM-32F PN 50055:C 03/20/01

Features

LDM-32F

The Lamp Driver Module LDM-32F has 32 alarm lamp/LED driver outputs
which sink current to system common (–) on activation. A single positive (+)
voltage is required to supply total operating power for all lamps or LEDs when
all drivers are activated. The LDM-32F provides a separate driver for system
trouble and inputs for a local lamp test switch. A maximum of 16 external
control switches may be wired to the LDM-32F. DIP switch SW3 is used to
enable or disable the onboard piezo, enable remote switch functions, select a
flashing LED function for new alarms and troubles, and other functions.
Switch SW4 is used to configure the module to annunciate 32 alarms or 16
troubles. A green

ON

LINE

LED flashes to indicate ongoing communications

with the host FACP. One LDM-32F supports up to 3 LDM-E32F modules. The
LDM-32F is supplied with 4 standoffs and screws for mounting to a CHS-4L
chassis or custom backbox.

Figure 1 LDM-32F

J10

J9

J2

LAMP
POWER

SWITCH
MATRIX

KEYSWITCH

ON LINE

J11

J5

J6

J7

J8

J4

J1

SW1

SW2

SW3

SW4

TB2

TB1

2

2

3

3

4

4

5

6

7

1

1

Not Used

Lamp Power
(+24 VDC)

System Trouble

Ribbon Cable
Connection to
LDM-E32F

Indicates EIA-485
Communication
Active

Output Connectors
for Wiring to LEDs

Lamp Power
(+5 VDC)

Security Key

Switch Terminal

Control Switch

Terminal

Address

Switches

Programming

DIP Switch

Alarm or
Alarm/Trouble
Slide Switch

EIA-485

Terminal

24 VDC

Power

Terminal

LD

M

-32F

.cdr

Advertising