Appendix C: MS-9600

Configuration

52

LDM-32F PN 50055:C 03/20/01

Configuration

Setting Rotary Switches

LDM Address Switches (SW1 & SW2) must be set to an address. Use the
following table to set these switches.

Note: Do not omit any address when annunciating 636 points or the MS-9600 will indicate
a constant trouble.

M = Module D = Detector

Table 23 SW1 & SW2 Switch Settings

Note: If a UDACT-F is installed and selected in control panel programming, it will
automatically assign addresses 20 - 31 to the UDACT-F and disable the selection of
these addresses.

FACP

Address

SW1

SW2

Relay Activation for:

1

0

1

8 System Points & Zones 1-56

2

0

2

Zones 57-99 & 2 NACs

3

0

3

Loop 1, Address M1 - M64

4

0

4

Loop 2, Address M1 - M64

5

0

5

Loop 1, Address M65 - M128

6

0

6

Loop 2, Address M65 - M128

7

0

7

Loop 1, Address M129 - M159 &
Loop 2, Address M129 - M159

8

0

8

Loop 1, Address D1 - D64

9

0

9

Loop 2, Address D1 - D64

10

1

0

Loop 1, Address D65 - D128

11

1

1

Loop 2, Address D65 - D128

12

1

2

Loop 1, Address D129 - D159 &
Loop 2, Address D129 - D159

13 - 19

Not Used

20

2

0

8 System Points & Zones 1-56

21

2

1

Zones 57-99 & 2 NACs

22

2

2

Loop 1, Address M1 - M64

23

2

3

Loop 2, Address M1 - M64

24

2

4

Loop 1, Address M65 - M128

25

2

5

Loop 2, Address M65 - M128

26

2

6

Loop 1, Address M129 - M159 &
Loop 2, Address M129 - M159

27

2

7

Loop 1, Address D1 - D64

28

2

8

Loop 2, Address D1 - D64

29

2

9

Loop 1, Address D65 - D128

30

3

0

Loop 2, Address D65 - D128

31

3

1

Loop 1, Address D129 - D159 &
Loop 2, Address D129 - D159