Configuration

Appendix B: MS-9200

LDM-32F PN 50055:C 03/20/01

47

Alarm /Trouble Annunciation of Points

The table below (also see Figure 30 on page 44) illustrates the configuration
of the LDM Series modules to annunciate the alarm and trouble states for all
99 points (detectors or modules) with the first eight points of address ‘01’
dedicated to the MS-9200 system functions (see Figure 31 on page 44).

Detectors

Set address ‘01’ and ‘02’ for detectors.

Table 19 Alarm/Trouble Setup - Detectors

Modules

Set address ‘03’ and ‘04” for modules

Table 20 Alarm/Trouble Setup - Modules

LDM Module
Address ‘01’

LDM Output Connectors

J5

J6

J7

J8

LDM-32F

System Functions

1 to 4

5 to 8

1st LDM-E32F

9 to 12

13 to 16

17 to 20

21 to 24

2nd LDM-E32F

25 to 28

29 to 32

33 to 36

37 to 40

3rd LDM-E32F

41 to 44

45 to 48

49 to 52

53 to 56

LDM Module
Address ‘02’

LDM Output Connectors

J5

J6

J7

J8

LDM-32F

57 to 60

61 to 64

65 to 68

69 to 72

1st LDM-E32F

73 to 76

77 to 80

81 to 84

85 to 88

2nd LDM-E32F

89 to 92

93 to 96

97 to 99

Not Used

LDM Module
Address ‘03’

LDM Output Connectors

J5

J6

J7

J8

LDM-32F

1 to 4

5 to 8

9 to 12

13 to 16

1st LDM-E32F

17 to 20

21 to 24

25 to 28

29 to 32

2nd LDM-E32F

33 to 36

37 to 40

41 to 44

45 to 48

3rd LDM-E32F

49 to 52

53 to 56

57 to 60

61 to 64

LDM Module
Address ‘04’

LDM Output Connectors

J5

J6

J7

J8

LDM-32F

65 to 68

69 to 72

73 to 76

77 to 80

1st LDM-E32F

81 to 84

85 to 88

89 to 92

93 to 96

2nd LDM-E32F

97 to 99

Not Used

Not Used

Not Used

Advertising