Alarm only annunciation of points, Alarm/trouble annunciation of points – Fire-Lite LDM-32F Lamp Drivers User Manual

Page 56

Advertising
background image

Appendix C: MS-9600

Configuration

56

LDM-32F PN 50055:C 03/20/01

Alarm Only Annunciation of Points

The following table displays an example of setting up an LDM Series to
annunciate the control panel’s SLC Loop #1, Modules M65 to M128 in
Alarm Only mode.

By referring to Table 23 on page 52 it can be determined what address can be
set to annunciate any other group of address points.

Table 28 Alarm Only Setup

Alarm/Trouble Annunciation of Points

The following table displays an example of setting up an LDM Series to
annunciate the control panel’s SLC Loop #1, Modules M65 to M128 in
Alarm/Trouble mode. (See Figure 36 on page 55).

By referring to Table 23 on page 52 it can be determined what address can be
set to annunciate any other group of address points.

Table 29 Alarm/Trouble Setup

LDM Module
Address ‘05’
(SLC Loop #1)

LDM Output Connectors

J5

J6

J7

J8

LDM-32F

M65 to M72

M73 to M80

M81 to M88

M89 to M96

LDM-E32F

M97 to M104

M105 to M112

M113 to M120

M121 to M128

LDM Module
Address ‘05’
(SLC Loop #1)

LDM Output Connectors

J5

J6

J7

J8

LDM-32F

M65 to M68

M69 to M72

M73 to M76

M77 to M80

1st LDM-E32F

M81 to M84

M85 to M88

M89 to M92

M93 to M96

2nd LDM-E32F

M97 to M100

M101 to M104

M105 to M108

M109 to M112

3rd LDM-E32F

M113 to M116

M117 to M120

M121 to M124

M125 to M128

Advertising