Switch settings, Mode switch - sw4, Installation configuring the ldms 26 – Fire-Lite LDM-32F Lamp Drivers User Manual

Page 26

Advertising
background image

2. Installation

Configuring the LDMs

26

LDM-32F PN 50055:C 03/20/01

Switch Settings

1 - Not Used: This switch must be set “OFF”
2 - Expanders Installed: None = OFF; One = ON; Two = OFF; Three = ON
3 - Expanders Installed: None = OFF; One = OFF; Two = ON; Three = ON
4 - Eight-Point Shift: Set switch “ON” to switch the FACP LED function
annuciation from the first eight annunciator positions on the LDM-32F to the
last LDM-E32F expander positions 57 - 64. This shift can only be set on an
LDM-32F set for address 01 (system using 56, or less, software zones).
5 - Receive Only: Set this switch “ON” for each LDM series that will provide
the same information as another LDM series in a different physical location.

Note: When two or more LDM series hold the same address, all but one must be
configured as “Receive Only”.

6 - Piezo Disable: Set this switch “ON” to disable the piezo from sounding for
any event. (The piezo will also be disabled if Flash Inhibit is “ON”.)
7 - Switch Inhibit: To disable the point control switches on the LDMs from
functioning, set this switch “ON”. When inhibited, the local lamp test switch
continues to function. In addition, the acknowledge/lamp test switch will
function only in a local capacity, unrecognized by the host FACP.
8 - Flash Inhibit: Set this switch “ON” to disable the flashing of LEDs
associated with unacknowledged events. Flash Inhibit also disables the piezo
from sounding.

Mode Switch - SW4

Set the mode of operation to:

“Alarm/Trouble” by sliding the switch to the right
“Alarm Only” mode by sliding the switch to the left.

Figure 19 Mode Select Switch - SW4

Alarm Only

Mode

Alarm/Trouble
Mode

LD

M32F

-S

W

4

.cdr