2. Installation

Wiring the Control Switch

24

LDM-32F PN 50055:C 03/20/01

Wiring the Control Switch

Each LDM must be set for Alarm/Trouble mode by positioning slide switch
SW4 to the right, for the optional control switches to function (the
acknowledge/lamp test switch will work in either mode). In this configuration,
each LDM-32F and LDM-E32F provides 16 alarm drivers, 16 trouble drivers
and 16 control switches. The alarm and trouble drivers are assigned to host
FACP zones/points via user setup. Not all switches must be used - switches can
be wired only for desired functions.

• Switches must be UL listed to switch 5 volts DC @ 0.5mA.
• Switches must be key-lock type, secured in a locked enclosure or a

security key switch must be installed to control access.

• All switches must be installed in the same room as, and no more than

20 feet from, the LDM enclosure. Wiring must be in conduit.

• Optional zone/point control switches must be momentary type.
• Use the cables supplied in the cable kit to wire the control switches.
• See Appendices for specific FACP information.

Figure 16 Optional Zone/Point Control Switch Wiring

12

3

4

5

6

78

J5

J4

J1

SW1

SW2

SW3

SW4

SWITCH
MATRIX

L

d

m

s

wtwr

.cd

r

Switch #16

Switch #15

Switch #14

Switch #13

Switch #12

Switch #11

Switch #10

Switch #9

Switch #8

Switch #7

Switch #6

Switch #5

Switch #4

Switch #3

Switch #2

Switch #1

Lamp Test/Acknowledge
Switch (momentary)

Manual Evacuate

System Reset

Signal Silence

Acknowledge

Note: Switches 5 - 16 are not used in this example.