Lamp/led driver operation – Fire-Lite LDM-32F Lamp Drivers User Manual

Page 35

Advertising
background image

Lamp/LED Driver Operation

Appendix A: Sensiscan 2000

LDM-32F PN 50055:C 03/20/01

35

Lamp/LED Driver Operation

LDM Address Switches (SW1 & SW2) must be set to address ‘01’.

Lamp Driver outputs do not latch - they track or follow the status of each zone/
point that they are assigned to annunciate. The table below defines the ON
status of each lamp driver output.

Note: Control Switches marked 'Not Used' will still function as local LAMP TEST or local
ACKNOWLEDGE switches for their respective points.

Note: If Alarm Only mode is selected, column labeled Yellow LED is not applicable and
control switches do not function.

Table 4 Annunciator Point Assignment to LDMs

CPU Points

1

1. If the 8-Point Shift (DIP switch #4 of SW3) is set ON, the eight Sensiscan 2000 CPU

functions (ACK, SIL, RESET, LAMP TEST, NAC1, NAC2, MUNTIE, RELAY) will be
shifted from annunciator points 1 through 8 (as shown above) to points 57 through 64
(provided those points exist in the system and the LDM-32F is set to address 01).

Alarm

(Red LED)

Trouble/Supv
(Yellow LED)

Control Switches

2

2. Optional control switches are active only if all of these conditions are met:

a) '8-Point Shift' (DIP switch #4) is set to OFF.
b) Receive Only (DIP Switch #5) is set to OFF.
c) Switch Inhibit (DIP Switch #7) is set to OFF.

Annunciator
Point #1

System Alarm

System Trouble

Acknowledge

Annunciator
Point #2

Not Used

Signal Silence

Signal Silence

Annunciator
Point #3

Not Used

Not Used

System Reset

Annunciator
Point #4

Not Used

Supervisory
Condition

Not Used

Annunciator
Point #5

NAC #1 Activated

3

3. Use green LEDs to indicate activation on controlled output circuits.

Trouble Status of
Circuit

NAC #1

Annunciator
Point #6

NAC #2 Activated

3

Trouble Status of
Circuit

NAC #2

Annunciator
Point #7

Remote Signaling
of Municipal Tie

Activated

3

Trouble Status of
Circuit

Remote Signaling
of Municipal Tie

Annunciator
Point #8

Alarm Relay

Activated

3

Module Trouble,
Power Failure, or
Disabled Circuit

Alarm Relay