Wiring the Power Terminal Block

2. Installation

LDM-32F PN 50055:C 03/20/01

19

Wiring the Power Terminal Block

24 VDC Power and Earth Ground

24 VDC power supplied to the LDM must be power-limited. This power is
inherently supervised (loss of power also results in a communication failure at
the control panel).

• Limit the total wire resistance to 10 ohms.
• Connect the Grounding Cable from the chassis to the earth ground

terminal of TB1 (

EARTH

).

• Connect 24 VDC power to the

POWER

IN

(+) and

COMMON

IN

(–)

terminals of TB1.

Figure 7 24 VDC Power Terminals - TB1

Wiring of multiple LDM-32F modules.

Figure 8 Multiple Module Wiring - 24 VDC

T B 1

N.C. Supervision
Inputs

Common In (–)
Common Out (–)
Power In (+24 VDC)
Power Out (+24 VDC)
Earth

24 VDC

Power

LD

M3

2F-

T

B

1

.cdr

Grounding Cable

– 2 4 V D C

+ 2 4 V D C

T B 1

T B 1

Host FACP or Remote
Power Supply

First LDM-32F -- -- -- -- -- -- -- Last LDM-32F

LD

M32

F

-p

ow

er.cd

r