Appendix B: MS-9200

Configuration

42

LDM-32F PN 50055:C 03/20/01

Configuration

The control panel needs to be programmed to either “Points” or “Zones”,
depending on which type of address is to be annunciated.

LDM Address Switches (SW1 & SW2) must be set to address ‘01’, ‘02’, ‘03’
or ‘04’. The CPU will differentiate between the addresses.

• For Zones use address 01 (56 zones).
• For Points use addresses 01, 02, 03 and 04 (198 points).

Note: Do not omit any address when annunciating 198 points or the MS-9200 will indicate
a constant trouble.

Alarm Only Annunciation of Zones

The table below illustrates the configuration of the LDM Series modules to
annunciate the alarm state of all 56 software zones (no zone troubles), and two
NACs, with the first eight points of address ‘01’ dedicated to the MS-9200
system function LEDs (see Figure 29 below).

Table 11 Alarm Only Setup

Alarm Only Annunciation of Zones - With 8-Point Shift

The table below illustrates the configuration of the LDM Series modules to
annunciate the alarm state of all 56 software zones (no zone troubles), and two
NACs, with the last eight points of address ‘01’ dedicated to the MS-9200
system function LEDs (see Figure 29 below).

Table 12 Alarm Only Setup with Shift

Figure 29 System Functions to Output Connectors - 1

LDM Module
Address ‘01’

LDM Output Connectors

J5

J6

J7

J8

LDM-32F

Sys Funct

Z1 to Z8

Z9 to Z16

Z17 to Z24

LDM-E32F

Z25 to Z32

Z33 to Z40

Z41 to Z48

Z49 to Z56

LDM Module
Address ‘01’

LDM Output Connectors

J5

J6

J7

J8

LDM-32F

Z1 to Z8

Z9 to Z16

Z17 to Z24

Z25 to Z32

LDM-E32F

Z33 to Z40

Z41 to Z48

Z49 to Z56

Sys Funct

1

2

3

4

5

6

7

8

J5

25

26

27

28

29

30

31

32

J8

System Alarm

System Alarm

Not Used

Not Used

LD

M3

2F-

J

5J8.cdr