6. Recording modes

List of recording modes

Recording

mode

Details

To check:

P.26

Condition,

Intermittent

leakage

P.27

Occurrence of

leakage

P.28

Intermittent

leakage,

Occurrence of

leakage

P.29

Waveform

Can record:

60,000 data(1ch)
20,000 data(3ch)

4,800 data(1ch)
1,600 data(3ch)

990 data(1ch)
330 data(3ch)

345 data

Available CH

3 channels at the same time

----

CH1 only

Recording

interval

15-kind:

1 sec. to 60 min.

0∼1000mA (can be set at every 1mA)

Pre-set

current value

----

Approx. 0.1 sec. (constant)

Current detection:

approx. 0.56mS

RMS:approx.

1.11mS

Measureme

nt interval

Pre-set recording

interval

(intermittent

measurement)

Current detection:

approx. 1.67mS

RMS:

approx. 3.33mS

Constantly until current detection

Sampling

cycle

At 50Hz:

approx. 0.222mS

At 60Hz:

approx. 0.185mS

Sampling

period

For 2 cycles

(50Hz: for 40mS)

When the pre-set current value is exceeded. (irregular)

Record

timing

At every recording

interval

Current detection:

Average value (Convert the Peak value (sine) to RMS)

Record/Display: True RMS

Measuring

method

True RMS

One-time

system

O N : Recording stops when memory becomes full.
OFF: Overwrite the old data, and store the latest data.

Battery life

Approx. 25 days (M-5000)/ Approx. 40 days (M-5001)

Continuous

recording

Event recording

Max. value

recording

Capture

recording