Features and Benefits

1.3

Features and Benefits

UV/IR Dual Sensor

High Speed Response: 150msec. response to saturated signal

Built In Test (BIT): Manual and Automatic (see Built-In-Test (BIT) on

page 16).

Heated Window: Prevents effects of icing, snow, condensation.

Electrical Interface:

Dry contact relays

Communication network RS-485

0-20mA output

HART Protocol: Communication protocol (see HART Protocol on page 6).

Exde: Integral junction box for easy wiring.

SIL-2: TÜV approved (models 40/40LB and L4B only).

Hazardous Area Certification: ATEX, IECEx, FM, CSA.

Functionality Approval:

EN54-10 approved by VdS

FM approved per FM3260

1.4

Principles of Operation

This section describes the 40/40L, LB, L4, L4B principles of operation and
includes:

Detection Principles, page 4

Heated Optics, page 5

HART Protocol, page 6

RS-485 Modbus, page 6

Product Certification, page 6

1.4.1 Detection Principles

The Model 40/40L, LB, L4, L4B Flame Detector is an electronic device

designed to sense the occurrence of fire and flames and subsequently
activate an alarm or an extinguishing system directly or through a control
circuit.