7 connecting the detector, Connecting the detector – Spectrex 40/40L-LB UV/IR Flame Detector Series User Manual

Page 38

Advertising
background image

SharpEye

TM

UV/IR Flame Detector User Guide

26

Connecting the Detector

To install the Tilt Mount and Detector:

1

Place the tilt mount in its designated location and secure it with four (4)
fasteners through four (4) holes 7 mm in diameter. Use the four (4)
screws and spring washers according to the kit.

Note: Removing the detector for maintenance purpose does not require

the Tilt Mount to be removed.

2

Unpack the detector.

3

Place the detector with its conduit/cable entries pointing downwards on
the holding plate of the tilt mount. Secure the detector with

5

/

16

" 18 UNC

x 1" screw to the tilt mount.

4

Release the Horizontal and Vertical Locking Screws using

3

/

16

" Hex Key

such that the detector can be rotated. Point the detector towards the
protected area and make certain that the view of the area is
unobstructed. Secure the detector in that position by tightening the
locking screws on the tilt mount. (Make sure the detector is in the

correct position.)

The detector is now correctly located, aligned and ready to be connected

to the system.

2.7

Connecting the Detector

This section describes how to connect the electric cabling to the detector

(Figure 7).

To connect the detector to the electrical cables

1

Disconnect the power.

2

Remove the back cover of the detector by removing three (3) socket

head-screws in the cover bolts. The terminal chamber is now revealed.

3

Remove the protective plug mounted on the Detector Conduit/Cable

entry; pull the wires through the Detector Inlet.

Advertising