2 cone of vision, Cone of vision, Figure 1: horizontal field of view – Spectrex 40/40L-LB UV/IR Flame Detector Series User Manual

Page 21: Table 3: fuel sensitivity ranges

Advertising
background image

TM 40/40L, Rev (6) February 2013

Performance Considerations

9

Table 3: Fuel Sensitivity Ranges

Type Of Fuel

Max. Distance (ft./m)

L/LB

L4/L4B

Gasoline

50/15

66/20

N-Heptane

50/15

66/20

JP5

37/11

49/15

Kerosene

37/11

49/15

Diesel Fuel

37/11

49/15

Alcohol 95%

25/7.5

39/12

IPA

25/7.5

52/16

Methanol

25/7.5

39/12

Methane

15/4.5

26/8

LPG

15/4.5

23/7

Paper

15/4.5

23/7

Polypropylene

15/4.5

16/5

Hydrogen

15/4.5

-

1.5.2 Cone of Vision

Horizontal: 100°

Figure 1: Horizontal Field of View