2 automatic bit, 3 manual bit, Table 9: results of a successful bit – Spectrex 40/40L-LB UV/IR Flame Detector Series User Manual

Page 29: Table 10: results of an unsuccessful bit, Manual bit

Advertising
background image

TM 40/40L, Rev (6) February 2013

Internal Detector Tests

17

1.6.2.2 Automatic BIT

The detector automatically performs a BIT every 15 minutes. A successful

BIT sequence does not activate any indicator.

The results of a successful and unsuccessful BIT are listed in Table 9 and
Table 10.
Table 9: Results of a Successful BIT

Output

Result

Fault relay

Wiring options 1, 2, 4: remains CLOSED

Wiring options 3 and 5: remains OPEN

0-20mA

output

Wiring option 1, 2, 3: Normal (4 mA)

Power LED

Green, Flashing, 1 Hz On (Normal)

Table 10: Results of an Unsuccessful BIT

Output

Result

Fault relay

Wiring option 1, 2, 4: changes to Open

Wiring option 3 and 5: changes to Closed

0-20mA output Wiring option 1, 2, 3: BIT Fault (2mA)
Power LED

Yellow, Flashing, 4 Hz

BIT procedure

Performed every 1 minute

1.6.2.3 Manual BIT

The BIT is manually initiated by momentarily connecting Terminal 3 with
Terminal 2 (or a switch across these terminals in the safe area).

If the BIT is unsuccessful, all outputs will function as described for

Automatic BIT, but the BIT is now automatically executed every 1 minute.
This continues until a successful BIT occurs, when the detector will resume
normal operation.
The results of a successful and unsuccessful Manual BIT are listed in
Table 11 and Table 12.