3 false alarms prevention, False alarms prevention, Table 4: immunity to false alarm sources – Spectrex 40/40L-LB UV/IR Flame Detector Series User Manual

Page 23

Advertising
background image

TM 40/40L, Rev (6) February 2013

Performance Considerations

11

1.5.3 False Alarms Prevention

To prevent false alarms, the detector will not alarm or react to the radiation
sources specified in Table 4.

Table 4: Immunity to False Alarm Sources

Radiation Source

Immunity
Distance ft. (m)

Indirect or reflected sunlight

IAD

Vehicle headlights (low beam) conforming to

MS53023-1

IAD

Incandescent frosted glass light, 300 W

IAD

Fluorescent light with white enamel reflector, standard
office or shop, 70 W (or two 35 W)

IAD

Electric arc [12mm (

15

/

32

") gap at 4000 V alternating

current, 60 Hz]

IAD

Arc welding [6 mm (

5

/

16

") rod; 210 A]

9.8 (3)

Ambient light extremes (darkness to bright light with

snow, water, rain, desert glare and fog)

IAD

Bright colored clothing, including red and safety

orange

IAD

Electronic flash (180 watt-seconds minimum output)

IAD

Movie light, 625 W quartz DWY lamp (Sylvania S.G.-55

or equivalent)

>6.5 (2)

Blue-green dome light conforming to M251073-1

IAD

Flashlight (MX 991/U)

IAD

Radiation heater, 3000 W

IAD

Radiation heater, 1000 W with fan

IAD

Quartz lamp (1000 W)

12 (4)

Mercury vapor lamp

IAD

Grinding metal

3.3 ft. (1)

Lit cigar

IAD

Lit cigarette

IAD

Match, wood, stick including flare up

3.3 ft. (1)

Notes:

IAD = Immune at Any Distance.

All sources are chopped from 0 to 20 Hz.