Electrical specifications, Outputs, Table 19: electrical specifications – Spectrex 40/40L-LB UV/IR Flame Detector Series User Manual

Page 56: A.2 electrical specifications, A.3 outputs

Advertising
background image

SharpEye

TM

UV/IR Flame Detector User Guide

44

Outputs

Sensitivity Ranges

1ft

2

(0.1m

2

) n-heptane pan fire from 50 ft. (15m) for models

40/40L-LB
1ft

2

(0.1m

2

) n-heptane pan fire from 66 ft. (20m) for models

40/40L4-L4B

Fields of View

Horizontal 100

, Vertical 95

Built-In-Test (BIT)

Automatic (and Manual)

A.2

Electrical Specifications

Table 19: Electrical Specifications

Operating
Voltage

Status

All
Outputs

Without
0-20mA

Power

Consumption
(Max. 24VDC)

Normal

1.61W

1.56W

Normal when Heater On

2.28W

2.16W

Alarm

2.64W

2.28W

Alarm when Heater On

3.24W

2.88W

Maximum Current

(Max. 24VDC)

Normal

70mA

65mA

Normal when Heater On

95mA

90mA

Alarm

110mA

95mA

Alarm when Heater On

135mA

120mA

Power

Consumption
(Max. 18-32VDC)

Normal

1.95W

1.85W

Normal when Heater On

2.56W

2.45W

Alarm

3.04W

2.56W

Alarm when Heater On

3.68W

3.2W

Maximum Current

(18-32VDC)

Normal

90mA

85mA

Normal when Heater On

105mA

100mA

Alarm

130mA

115mA

Alarm when Heater On

160mA

145mA

Electrical Input Protection The input circuit is protected against

voltage-reversed polarity, voltage transients,
surges and spikes according to MIL-STD-
1275B

A.3

Outputs

Electrical

Interface

There are five output-wiring options. These options must

be defined at the factory per the customer order and
cannot be changed at the customer facility.
See General Instructions for Electrical Wiring on page 49
for the wiring/terminal diagram for each option.
Unless otherwise specified, the default is Option 1. The

Advertising