Table 18: Troubleshooting Table

Problem

Cause

Corrective Action

LEDs Off
Fault Relay at N.O

0-20mA at 0mA

No power at the
unit

Check that the correct power
is sent to the detector.

Check power polarity.

Check wiring in the detector.

Send the detector back for

repairs.

Yellow LED flashes

at 4 Hz
Fault Relay at N.O
0-20mA at 0mA

Fault Detector

Low Voltage

Faulty Detector

Check the voltage at the

detector; verify at least 24V
at the detector terminal.

Send the detector back for
repairs.

Yellow LED flashes

at 4 Hz
Fault Relay at N.O
0-20mA at 2mA

BIT Fault

Faulty Detector

Clean detector window.

Re-power the detector.

Replace the detector.

Red LED
constantly on

If no fire exists,
then, detector

alarm latched

Perform Reset to the detector.

Alarm Relay at On
0-20mA at 20mA

Alarm condition

Check cause for alarm.

If no alarm, re-power the
detector.

Send the detector back for
repairs.