1 verifying the detector wiring, Verifying the detector wiring, Table 14: model 40/40l, lb, l4, l4b wiring options – Spectrex 40/40L-LB UV/IR Flame Detector Series User Manual

Page 40: Table 14

Advertising
background image

SharpEye

TM

UV/IR Flame Detector User Guide

28

Connecting the Detector

2.7.1 Verifying the Detector Wiring

The detector has five output wiring options within the Exde integral terminal
section of the enclosure. There are 12 terminals labeled 1-12.

Table 14 describes the function of each terminal for all the wiring options.
Table 14: Model 40/40L, LB, L4, L4B Wiring Options

Wire

Terminal
No.

Option 1
Default

Option 2

Option 3

Option 4

Option 5

1

+24 VDC

+24 VDC

+24 VDC

+24 VDC

+24 VDC

2

0 VDC

0 VDC

0 VDC

0 VDC

0 VDC

3

Manual

BIT

Manual

BIT

Manual

BIT

Manual

BIT

Manual

BIT

4

Fault

Relay N.C.

Fault

Relay N.C.

Fault

Relay N.O.

Fault

Relay N.C.

Fault

Relay N.O.

5

6

Alarm

Relay N.O.

Alarm

Relay N.O.

Alarm

Relay N.O.

Alarm

Relay N.O.

Alarm

Relay N.O.

7

Alarm

Relay C

Alarm

Relay C

Alarm

Relay C

Alarm

Relay C

Alarm

Relay C

8

0-20mA

In

Alarm

Relay N.C.

Alarm

Relay N.C.

Auxiliary

N.O.

Auxiliary

N.O.

9

0-20mA

Out

0-20mA

Out*

0-20mA

Out*

Auxiliary

C

Auxiliary C

10

RS-485+

(1)

RS-485+

(1)

RS-485+

(1)

RS-485+

(1)

RS-485+

(1)

11

RS-485-

(1)

RS-485-

(1)

RS-485-

(1)

RS-485-

(1)

RS-485-

(1)

12

RS-485

GND

RS-485

GND

RS-485

GND

RS-485

GND

RS-485

GND

*Available with the HART protocol.
Notes:

RS-485 is used for communication network as specified in Appendix C

(Terminals 10, 11, 12) and to connect (in safe area) to PC/Laptop for
configuration/diagnostics.

Alarm relay:

N.O. energized contact in wiring options 1, 4, 5.

N.O. and N.C. energized in options 2 and 3.

0-20mA is ‘Sink’ in option 1 and ‘Source’ in option 2 and 3.

0-20mA 'Source' in options 2 and 3 available with the HART protocol.

In Wiring Option 1, link Terminals 1 and 8 to change the mA output to
‘Source’.

Advertising