2 fm, csa, 4 en54-10, Fm, csa – Spectrex 40/40L-LB UV/IR Flame Detector Series User Manual

Page 19: Sil-2 approved (tüv) (models 40/40lb and l4b only), En54-10

Advertising
background image

TM 40/40L, Rev (6) February 2013

Principles of Operation

7

Ex de IIC T4 Ta -55°C to +85°C

Ex tD A21 IP66/X7 T105°C

This product is suitable to use in hazardous zones 1 and 2 with IIC gas

group vapors present.

1.4.5.2 FM, CSA

The 40/40L, LB, L4, L4B Flame Detector is certified to FM and CSA Explosion
Proof and Functionality per FM3260:

Class I, Division 1, Groups B, C and D, T5 Ta = 85°C.

Dust Ignition Proof – Class II/III Division 1, Groups E, F and G.

Ingress Protection – IP67, IP66, NEMA 250 Type 6P.

For more details see FM Report Project ID3029553 and CSA Report No.

2451134.

1.4.5.3 SIL-2 Approved (TÜV) (Models 40/40LB and L4B only)

The 40/40LB, L4B Flame Detector is certified to SIL-2 requirement per IEC

61508.4, Chapter 3.5.12.

The alert condition according to SIL-2 can be implemented by:

Alert signal via 0-20mA current loop.

or

Alert signal via alarm relay and fault relay.

For more details and guidelines for configuring, installing, operating and

service – see SIL-2 Features on page 65 and TÜV Report No.
968/EZ348.00/009.

1.4.5.4 EN54-10

The 40/40L, LB, L4, L4B Flame Detector is certified to EN54-10 and CPD.

The detector has been tested and approved per EN54-10 by VdS.

This test includes functional test, environmental test, EMI/EMC test and

software check.

For more details see VdS Report No. BMA 12120 for models 40/40L-LB
and Reports No's. BMA 12120 and BMA 12121 for models 40/40L4-L4B.

Advertising